Leave Your Message
Low Smoke Zero Halogen Irradiated Insulating Cable Material - High-Quality China Suppliers and Factory

Low Smoke Zero Halogen Irradiated Insulating Cable Material - High-Quality China Suppliers and Factory

Introducing our advanced low-smoke, halogen-free flame retardant wire and cable, designed with an array of impressive features including low toxicity, high-temperature resistance, and excellent weather resistance. Made from environmentally friendly materials, our products ensure high dielectric properties essential for safety and performance.

Our innovative irradiation crosslinking process utilizes a high-energy electron beam to transform the linear molecular structure of the insulation layer into a robust three-dimensional network. This creates a dense lattice that effectively prevents the combination of hydroxide and water molecules, enhancing the cable's durability. The result is superior temperature resistance, wear resistance, and enhanced flame-retardant performance, while also providing excellent water resistance. As a leading factory and supplier in China, we are committed to delivering high-quality solutions to meet your wiring needs.

    PRODUCT FEATURES

    Low smoke combustion This cable material produces less smoke in the event of a fire, which helps to improve the safety of personnel evacuation.
    High Flame retardant With good flame retardant performance, can slow the spread of fire, reduce fire losses.
    Low toxicity There are fewer harmful substances in the smoke produced, which is less harmful to human health.
    High temperature resistance Can maintain stable performance in high temperature environment, suitable for various industrial applications.
    Weather resistance It has the ability to resist ultraviolet light and climate change, which extends the service life of the cable.
    High dielectric property It has good electrical insulation performance, which can effectively prevent short circuit or fault of wire and cable.
    Environmental protection Does not contain harmful halogen compounds, helping to reduce the negative impact on the environment.

    SCOPE OF USE

    Cable and optical cable, coaxial cable, network cable, elevator cable, etc.

    TEST ITEMS AND STANDARDS

    Properties of halogen-free low smoke flame retardant thermoplastic polyolefin insulating materials and sheathing materials.

    No. Inspection item Unit Requirements
    WDZ-Y-J70 WDZ-Y-H70 WDZ-Y-H90
    1 Tensile strength MPa ≥10.0 ≥10.0 ≥10.0
    2 Elongation at break % ≥160 ≥160 ≥160
    3 Air aging chamber
    Aging temperature 100±2 100±2 110±2
    Aging time h 168 168 240
    Maximum rate of change of tensile strength % ±25 ±25 ±25
    Maximum rate of change of elongation at break % ±25 ±25 ±25
    4 Thermal deformation
    Test temperature 90±2 90±2 90±2
    Experimental result % ≤50 ≤50 ≤50
    5 20℃ volume resistivity Ω·m ≥1.0×1012 ≥1.0×1010 ≥1.0×1010
    6 Volume resistivity at operating temperature
    Test temperature 70±1
    Volume resistivity Ω·m ≥2.0×108
    7 Dielectric strength MV/m ≥20 ≥18 ≥18
    8 Heat shock test
    Test temperature 130±3 130±3 130±3
    Test time h 1 1 1
    Experimental result No cracking No cracking No cracking
    9 Impact embrittlement temperature
    Test temperature -25 -25 -25
    Experimental result Number ≤15/30 ≤15/30 ≤15/30
    10 Ozone resistance test
    Test temperature 25±2 25±2
    Experiment time h 24 24
    Ozone concentration ppm 250~300 250~300
    Experimental result No cracking No cracking
    11 Hot water immersion test
    Test temperature 70±2 70±2
    Experiment time h 168 168
    Maximum rate of change of tensile strength % ±30 ±30
    Maximum rate of change of elongation at break % ±35 ±35
    12 Oxygen index % ≥28 ≥30 ≥30
    13 Smoke density
    flameless ≤350 ≤350 ≤350
    flaming ≤100 ≤100 ≤100
    14 Combustion releases gas acidity
    HCI and HBr content % ≤0.5 ≤0.5 ≤0.5
    HF content % ≤0.1 ≤0.1 ≤0.1
    pH value ≥4.3 ≥4.3 ≥4.3
    Electric conductivity μS/mm ≤10 ≤10 ≤10
    15 Material smoke toxicity hazards According to the application requirements, negotiated by the supply and demand parties.

    CERTIFICATIONS

    FAQ

    What are the main features of this halogen-free cable material?

    The material offers low smoke combustion, high flame retardancy, low toxicity, high temperature resistance, excellent weather resistance, high dielectric properties, and is environmentally friendly.

    What is the typical scope of use for these materials?

    They are widely used in standard cables, optical cables, coaxial cables, network cables, elevator cables, and various other industrial applications.

    Does this cable material contain harmful halogens?

    No, it is a halogen-free material. It does not contain harmful halogen compounds, which helps reduce negative environmental impacts and improves safety during a fire.

    Can this material withstand high-temperature environments?

    Yes, it features high temperature resistance, maintaining stable performance even in demanding high-temperature industrial environments.

    What is the tensile strength requirement for the WDZ-Y-J70 model?

    According to our testing standards, the tensile strength requirement for the WDZ-Y-J70 material is ≥10.0 MPa.

    How is the material's smoke toxicity hazard determined?

    The material smoke toxicity hazards are evaluated and negotiated by the supply and demand parties based on the specific application requirements of the final product.